Key Properties:1. Inherit the simple structure of the traditional C cores2. Clamp-on core design, safer, easier installation, portable, don’t need to cut of the grid-power when adjust the inductance.3. Comparing
Other materials, with high accuracy, due to nanocrystalline high permeability.4. Energy conservation & environment protection, huge potential marketMain Application:Our Split-core current
Transformer can be mounted to existing panels, such as control centers or load centers, to measure or monitor wattage. Which is widely used for:· Current Measurement· Electrical loading monitoring· Energy and sub-metering products· Network equipment· Instruments and sensors· Control System· Go GREEN initiatives
Characteristic |
1 -Split core design, small core loss and high precision; |
2-There is no need to disconnect the bus, the installation of portable, does not affect the normal use of electricity to customers; |
3-Exquisite appearance, small size and light weight; |
4-buckle opening and closing structure, easy to open and close. |
Typical application |
1-Function: general testing and protection in power system with strong maneuverability or narrow space or uninterrupted power system. |
2-Application: test and protection of electric instrument, electronic multifunctional watt-hour meter and field calibrator. |
Electrical character | |
1-Equipment maximum voltage: 720V | |
2-Power frequency voltage:4000V50Hz/1min(1mA) |
3-Primary rated current:0-800A |
4-Secondary rated current:0-100mA |
5-Temperature range:-40℃-120℃ |
6-Temperature error :±2℃ |
7-Output voltage :3*220/380V |
8-Leader output definition: Lead number: 1:Orange, 2:Gray; 3:Yellow; 4:Black; 5:Empty feet; 6:Red.1-2Foot connection temperature measurement;3-4 feet connected to current transformer, yellow head and black tail;6 pin voltage |
9:Accuracy class :0.2% |
10:Frequency:50/60Hz |
Installation size |
Specifications | A(mm) | B(mm) | C(mm) | D(mm) | E(mm) | |
ECS-16 | 16 | 48 | 60 | 35 | 12 |
ECS-24 | 24 | 60 | 72 | 35 | 12 |
ECS-36 | 36 | 72 | 84 | 35 | 12 |
Essential parameter |
P/N | Primary rated current | Secondary rated current | Output voltage | Accuracy class |
ECS-16 | 0~100 | 0~100 | 3*220/380V | 0.2% |
ECS-24 | 0~400 | 0~100 | 3*220/380V | 0.2% |
ECS-36 | 0~800 | 0~100 | 3*220/380V | 0.2% |
Flexible Design:1. Various shape design supported
2. Our workshop produce form Split Core, to Split current Transformer
3. Customised Size as request. Our Common Standard CTs & dimentions for your first reference as below:
We can design & produce goods based on specifications & drawing, specification needed including:1. Bare core size, Size finished, special Min. Hole size.2. Split CT Turns ratio, accuracy Coilcore - Guangzhou Amorphous Electronic Technology Co.,ltd., established in 2009, our core competence is Nanocrystalline Core & Amorphous Core & Ferrite Core.
It has been a major manufacturer in Current Transformer & Sensor Industry. The certification to ISO9001:2015, SGS, FTA ensures that rigorous procedures are followed in all areas of operations. Like clients ABB,ALCE, ESITAS, SIGMA, RITZ, you can get our service of quickly service, stable quality, affordable cost, fast delivery.Our Partner:Top Supplier for Value Customers:
Manufacture:
Certificates:
Safe Package:
Contact us if you need more details on Split Core Dc Current Sensor. We are ready to answer your questions on packaging, logistics, certification or any other aspects about Clamp Type Current Transformer、Ring Core Current Transformer. If these products fail to match your need, please contact us and we would like to provide relevant information.
Product Categories : Transformer and Inductor > Split Core Current Transformer